FFU ULPA 15
Type SGE-EC
1210 x 600 x 335 mm
& individual sizes
Housing
- Dimensions (LxWxH) 1210 x 600 x 335 mm
- Steel (chrome-plated)
- 25kg (incl. filter and motor)
Pre-filter
- Dimensions (LxWxH) 495 x 495 x 15 mm
- Filter class ISO Coarse 90% (G4)
Main filter
- Dimensions (LxWxH) 1210 x 600 x 75 mm
- Material fiberglass
- Filter class ULPA 15
- Filter differential pressure (start) 80-135 Pa (depending on air velocity)
- Filter differential pressure (end) 270 Pa
- Separation efficiency 99.9995% (particle size 0.1-0.12 µm)
- Flow velocity* 0.45 m/s
- Air volume flow* 1100 m³/h
Motor/fan
- Motor type EC motor
- Power supply Single-phase 220V, 50Hz
- Control adjustable via display buttons or via Modbus
- Power consumption* 105 W
- Volume level* 62 dB(A)
Optional versions
- Digital pressure cell for differential pressure measurement
(for later evaluation of filter contamination and operating status) - Aerosol dispensing point
- Individual sizes on request
*When setting 80%
The SGE-EC filter fan unit features an energy-efficient EC motor and can be configured either directly via an on-board display or controlled via Modbus. Depending on the application, the FFU can also be equipped with a pressure cell and an aerosol dispensing port.
This type of filter can be supplied in individually selectable sizes on request.
SKU: 8011.5.956
Housing
- Dimensions (LxWxH) 1210 x 600 x 335 mm
- Steel (chrome-plated)
- 25kg (incl. filter and motor)
Pre-filter
- Dimensions (LxWxH) 495 x 495 x 15 mm
- Filter class ISO Coarse 90% (G4)
Main filter
- Dimensions (LxWxH) 1210 x 600 x 75 mm
- Material fiberglass
- Filter class ULPA 15
- Filter differential pressure (start) 80-135 Pa (depending on air velocity)
- Filter differential pressure (end) 270 Pa
- Separation efficiency 99.9995% (particle size 0.1-0.12 µm)
- Flow velocity* 0.45 m/s
- Air volume flow* 1100 m³/h
Motor/fan
- Motor type EC motor
- Power supply Single-phase 220V, 50Hz
- Control adjustable via display buttons or via Modbus
- Power consumption* 105 W
- Volume level* 62 dB(A)
Optional versions
- Digital pressure cell for differential pressure measurement
(for later evaluation of filter contamination and operating status) - Aerosol dispensing point
- Individual sizes on request
*When setting 80%